Description
⚡ Power & Topology
-
Rating: 6 kVA / 4.2 kW
-
Topology: Online, double-conversion (true sine-wave output)
-
Power Factor (output): 0.7
-
Efficiency: > 88% in normal mode; ECO mode higher
🔌 Input & Output
-
Input Voltage Range: 122 V – 300 V (wide immunity to fluctuations)
-
Input Frequency: 50 / 60 Hz (auto-sensing)
-
Voltage Regulation: ±1%
-
Output Voltage Options: 208 / 220 / 230 / 240 VAC
-
Crest Factor: 3:1
-
Critical Load Transfer Time: 0 ms (online UPS)
-
Bypass Configuration: Internal static bypass plus optional manual bypass
🛋 Battery & Runtime
-
Battery Type: Internal, sealed lead-acid (AGM), 20 × 12 V (240 VDC)
-
Cold-Start Support: Yes (can start on batteries alone)
-
Typical Runtime:
-
~19 minutes at full load (~4.2 kW)
-
Longer at reduced loads
-
-
Recharge Time: Typically <7 hours to 90% capacity
🧰 Communications & Monitoring
-
LED Indicator Panel: Utility, Inverter, Bypass, Fault, Load/battery bars
-
Communication Ports: RS‑232, Intelligent-Slot (for SNMP, AS/400, dry contacts), dry contacts
-
Parallel Capability: Supports up to 3 units in parallel (N+1 redundancy)
-
Software Compatibility: Eaton WinPower
🛠 Protection & Features
-
Input Power Factor: ≥ 0.98
-
Total Harmonic Distortion (THDi): <10%
-
Overload Handling:
-
105–125% load: holds ≥ 1 minute
-
125–150%: ≥ 10 seconds
-
150%: switches to bypass in <1 s
-
-
Generator compatibility: Yes
-
Audible & Visual Alarms for faults, low battery, overload, bypass
-
Automatic bypass in case of faults or overload
📏 Physical & Environmental
-
Form Factor: Tower
-
Dimensions (H×W×D): 717 × 260 × 570 mm
-
Weight: ~84 kg
-
Operating Temperature: 0 °C – 40 °C
-
Noise Level: <55 dB at 1 m
-
Humidity: 5–95% non-condensing
-
Altitude: Rated up to 1,000 m (higher altitudes require derating)